Understanding
In-Line RF Power Measurements
| |
 |
At a Glance |
 |
 |
 |
| Accurate energy demands on rf generating
equipment for semiconductor processing continue to grow. As IC geometries shrink, so do
process parameter tolerances. The actual amount, frequency spectrum and time duration of
rf energy applied to a process has become increasingly critical to process performance.
Power tolerances of 3-5% are no longer acceptable to many modern semiconductor processes. |
|
Paul Rummel,
Comdel, Gloucester, Mass.
Repeatable rf power delivery requires that an rf generator's internal power sensor be
repeatable and accurate in the plasma system environment . A generator's energy
delivery performance driving its intended plasma application may be quite different from
that of driving a broadband, resistive dummy load. To be of any diagnostic value, attempts
to monitor or verify energy delivery performance through the use of externally applied
in-line wattmeters requires an understanding of the measurement type and also requires
probable accuracy of the meter being used.
This article describes two commonly used methods of detecting rf power and the
implications of using those methods in a plasma system environment. The descriptions for
these two detection methods apply to both an rf generator's internal power detector and an
externally applied wattmeter. Next, a discussion of rf system harmonic energy sources
exposes potential added errors to the power measurement methods.
Power measurements in rf delivery systems
 |
| 1. A typical rf delivery system with some common points
for rf power measurement. |
Figure 1 shows a typical rf delivery system with some common
points for rf power measurement (1-4). In the rf generator block (rf gen), a power
amplifier produces a waveform that can be very high in harmonic content. This is typical
because high amplifier efficiencies can be realized if the waveform is not constrained to
the fundamental only. Because of the high amplifier harmonic content, a low-pass filter
(LPF) or band-pass filter (BPF) is typically used to attenuate energies at the harmonic
frequencies. Most commercial rf generators contain a power detector of some sort (circle
1) between the filter and the generator's output to monitor and control the forward or
delivered output power to a desired set point.
An rf plasma system may or may not utilize a transmission line (Xmission line) between
the rf generator and an impedance transformation (Z xfrm), or matching network circuit.
When a transmission line is used, two convenient power-monitoring points are at the line
termination points as shown as circles 2 and 3. These are common locations to insert a
commercial in-line power meter for diagnostic purposes.
A power measurement point between the impedance transformation circuit and the plasma
(circle 4) is shown as more of a side note. This location is often not a convenient in-line
power monitoring point because the voltages and currents can be quite high and only
specialty devices are used here.
These devices are typically built into the system, because connectors and added
components at this location introduce unwanted losses and reactances that can drastically
affect a process. Because of these added complications, in-line power monitoring at the
plasma load is beyond the scope of this article.
Diode peak-detectors
 |
| 2. The operation of forward and reflected diode
peak-detector circuits is shown. |
The most widely used power detection circuit is the diode peak-detector. This circuit
is commonly used for the internal power sensor in many rf generator designs and in many
commercially available in-line power meters. The basic diode peak-detector circuit is
comprised of components that provide an rf voltage sample summed with an rf current
sample, and then turned into a dc signal or "peak-detected" with a diode. Figure 2 illustrates the operation of forward and reflected diode
peak-detector circuits.
For the forward case, voltage and current samples are summed to produce a signal that
is detected with a diode to give a dc signal that is proportional to the square root of
forward power. Because voltage and current are both proportional to the square root of
power, so is the sum of voltage and current.
For the reflected case, the current sample is 180° out of phase with the actual
current being detected. This is easily accomplished by reversing the leads of a current
sampling transformer. If the power detector is designed for 50 W
load impedance, the voltage and current samples are designed to present equal amplitudes
at the summation point. If the detector is placed in a circuit that has a 50 W load, then these two samples will be of the same amplitude and
exactly out of phase with each other, giving a very small or zero summation signal. This
is also peak-detected to give a dc signal proportional to the square root of reflected
power.
Errors in the diode peak-detection method are due to several factors. First, diodes
used for detection have a nonlinear characteristic at low levels, which, for more accurate
detection circuits, must be accounted for. Second, the output signal must be squared
through either a squaring circuit or a mathematical algorithm, which can introduce more
errors. Third, the accuracy is highly dependent upon the peak value giving a true
representation of the fundamental power. Any small amount of harmonic energy present in
the rf being detected can misshape the waveform, introducing a large
"fundamental" detected power error.
Multiplier detectors
 |
| 3. Four-quadrant analog multipliers produce the
waveforms shown at the bottom of this figure by squaring the summed signals. |
As in the diode peak-detector described above, multiplier detectors use multiplication
circuits in place of the diode to produce dc signals directly proportional to
power. Figure 3 illustrates multiplier detector operation.
As in the diode peak-detector, voltage and current samples are summed. Where the
multiplier circuit differs is how the proportional dc signals are produced. Four-quadrant
analog multipliers are used to square the summed signals to produce the waveforms shown at
the bottom of the figure. Since the squared signals are no longer bipolar, a simple RC
integrating circuit is used to "average" the signals, providing dc levels
directly proportional to forward and reflected power. The relationship of the detectors'
outputs are directly proportional to power because the summed (square root
proportional) signals get squared in the process by the multipliers.
 |
| 4. In the "direct multiplier" detector, a
signal directly proportional to delivered power is obtained and then integrated to give
the proportional dc signal. |
Another variation of the multiplier detector is the "direct multiplier"
detector. In this circuit, a signal directly proportional to delivered (forward-reflected)
power is obtained by using a four-quadrant multiplier to directly multiply the voltage
sample by the current sample. The resulting signal is then integrated to give the
proportional dc signal. This method is illustrated in Figure 4.
This circuit has the advantage of providing a signal directly proportional to the
amount of energy dissipated in all loads after the detector. Though it does not give any
indication of the amount of reflected power from the load, this circuit can be used to
accurately provide power information into highly mismatched loads.
For both of these multiplier power detectors, errors can be introduced by the
nonlinearities of the four quadrant multipliers themselves. Also, the multipliers must
have sufficient speed or bandwidth to follow the sampled voltage and current waveforms.
Since the detected power signals are derived from the integration of the multiplied
waveforms (area under the curve), these types of detectors provide power signals
proportional to total forward or total delivered power. Total power means
the power detected at the fundamental frequency plus power in the harmonic
frequencies.
Harmonic energies in rf plasma systems
Harmonic energies found in rf-powered plasma-processing systems can be considered to
have two sources: 1) the rf generator and 2) the nonlinearities of the plasma.
Harmonic energy from the rf generator is easily comprehended as any harmonic energy
originating from a power amplifier that does not get completely rejected by the
generator's internal harmonic filter. Typical harmonic energy levels from commercial rf
power generators range from -20 dB to -50 dB (100 to 100,000 times less), from the amount
of energy in the fundamental frequency. For example, if an rf generator is specified to
have all harmonic energies -30 dB or more down from the fundamental, this means that, for
1 kW of power at the fundamental, no more than 1 W of output power is delivered at any of
the harmonic frequencies. This may also mean that the energies in all of the harmonics combined
do not sum to more than 1 W. In all cases, rf generator harmonic energies are
specified into a broadband resistive dummy load. This means that not only is the
fundamental loaded with 50 W, but so are each of the harmonic
energies. In many plasma system applications, only the fundamental energy gets resistively
loaded, while the harmonics see arbitrary reactive loads that can change with process and
matching network positions. This can result in harmonic energies directly due to the rf
generator far in excess of the generator's rated harmonic output .
The second source of plasma system harmonic energy can be much larger than the direct
contribution of the rf generator. This is a contribution from the nonlinearities of the
plasma itself. These nonlinearities convert fundamental energy into harmonic energy.
Unless specifically trapped or filtered, harmonic energies, emanating from the plasma, can
be supported and passed back through the matching network. These harmonic energies can
then mix with the already present generator contributed harmonic energies. It would not be
uncommon to find -20 dB of harmonic energy present along the transmission line of an rf
delivery system using an rf generator specified for -40 dB harmonic content. This harmonic
energy is either dissipated in the generator, transmission line, plasma, or simply remains
as stored energy distributed throughout the components of the rf delivery system.
Harmonic energy consequences
 |
| 5. The differences of diode peak-detected summation
samples as a function of the third harmonic phase relationship 20 dB below the
fundamental. |
The end result of these two sources of harmonic energy is that any power detector
sampling circuit with sufficient bandwidth will faithfully reproduce the actual rf voltage
and current waveforms, inclusive of the distortions caused by the harmonics. Multiplying
power detectors will detect the total energy (fundamental + harmonic). Diode peak-detector
power sensors can exhibit large errors based on the phase relationships between harmonic
voltages and currents, and the phase relationships between the harmonics and the
fundamental. To illustrate the extent to which a diode peak-detecting power sensor can be
affected, Figure 5 shows the differences of diode peak-detected
summation samples as a function of the third harmonic phase relationship to the
fundamental. It is assumed that the fundamental energy is perfectly terminated, (no
reflected fundamental power).
In this example, the two V+I sampled sine curves having the same fundamental energy get
distorted by the presence of third harmonic energy 20 dB below the fundamental. If the
harmonic voltage is in phase with the harmonic current, then the distortions shown in the
figure result. The flattened curve (0.9V peak) has the third harmonic energy in phase with
the fundamental, while the second curve (1.1V peak) has the third harmonic out of phase
with the fundamental. (If there were no harmonic distortion, the peak would be at 1V.) The
peak-detected values are then squared to represent power, resulting in 0.81V and 1.21V
signals. If the undistorted or fundamental power is represented by a 1V signal, then the
-20 dB harmonic energy adds in a potential -19% to +21% power error depending upon the
phase of the harmonic to fundamental energy. In reality, 20 dB down means that the energy
in the third harmonic is only 1% of that in the fundamental. For diode peak-detecting
power sensors, the added 1% of harmonic energy can create a potential ±20% power
measurement error.
In the above example only the effect of the third harmonic is shown. It is entirely
possible to have added errors from the combinations of other (second, fourth, fifth, etc.)
harmonic energies that add to the peak values. The phase relationships of harmonic
energies may be extremely difficult to predict or measure in any real rf delivery system.
The worst-case power measurement error should always be assumed based upon the total
harmonic energy content. This can be readily measured with a calibrated directional
coupler and spectrum analyzer at the point of power measurement.
Table 1 shows the worst-case errors of diode peak-detecting power readings for
different levels of harmonic distortion.
Table 1
Diode Peak-Detector Worst-Case Errors
|
| Harmonic
content |
Approx.
potential error |
| -20 dB |
±20% |
| -30 dB |
±6% |
| -40 dB |
±2% |
| -50 dB |
±0.6% |
| -60 dB |
±0.2% |
These potential errors should be added to the power meter's base accuracy. For
example, if an in-line power meter's specified accuracy is ± 3% with a specified maximum
harmonic content of -50 dB, then the accuracy tolerance due to harmonic content is ±0.6%.
That means that the base accuracy (no harmonic content) is ±2.4%. Thus, if the system
being measured has harmonic content -30 dB, then total expected accuracy is 2.4% + 6% =
±8.4%.
Conclusions
Without knowing the type of power detector used and the harmonic content present in an
rf-driven plasma-processing system, power measurements must be highly suspect. It may be
unrealistic to expect very low amounts of harmonic energy to be present in an rf delivery
system. It is equally unrealistic to predict system harmonic content based solely upon the
rf generator harmonic output specification from the manufacturer. Harmonic energy
management requires careful design considerations in all components that make up an rf
delivery system.
Harmonic energy by itself is not necessarily the direct cause of process
non-repeatability. An rf delivery system may have a large amount of harmonic energy
present that does not change amplitude or phase over process periods. This would result in
a fixed, repeatable power control error. But even in this case, diagnosing the system with
an in-line wattmeter can exhibit large power differences depending upon measurement
position along the transmission line. Also, the fixed error may be highly dependent upon
the actual rf system components used. Replacing a matching network could make a large
difference to harmonic phase relationships due to very minor manufacturing differences.
This could cause a large change to the previous fixed error.
Process non-repeatability can be the direct result of using the diode peak-detector to control
process power in the presence of high harmonic content. Even if an rf generator uses a
multiplier type or other power detection method that is immune to harmonic induced errors,
attempts to diagnose an rf system with an externally placed diode peak-detecting
wattmeter might only serve to cast doubt on the integrity of the system. Certainly, if
this type of power meter must be used, a calibrated spectrum analyzer measurement should
be included in the diagnosis to determine the error tolerance of the power reading.
Looking forward, there are two issues to achieving improved repeatability of rf power
measurements: the accuracy and repeatability of rf power control , and the accuracy
of added in-line diagnostic power meters. For this discussion, it is assumed that power
control is performed by the system rf generator (Fig. 1, circle 1),
and diagnostic power meters are inserted along the transmission line, (Fig. 1, circle 2 or 3). To achieve much lower rf power measurement
tolerances for this scenario, there are at least three approaches that can be taken:
- Attenuate harmonic energies at the points in the system where power measurements are
made.
- Decrease the sensitivity of diode type detectors to harmonic content.
- Use multiplier type power detectors.
Based on Table 1, it would require a diode peak-detecting power sensor to be exposed to
less than -50 dB of harmonic energy to be affected less than ±0.6%. Approach number one
would require that not only the rf generator's internal filter reject harmonics to this
degree, but also require a similar filter on the other side of the power sensor to reject
harmonics from the plasma side, (Fig. 1, circle 3). While this
double filtering would be effective for power control and in-line diagnostic
measurements, it could create further complications. The extra poles and zeroes of two -50
dB filters create the possibility of added resonances, which increases the potential for
instabilities. Also, the filter on the plasma side would have loss, (in addition to
matching network losses), which must now be accounted for in the process power
requirements.
Approaches two and three are similar in that they involve using power detection
circuits that are more immune to harmonic content error. High harmonic rejection in a
diode type detector results in power measurements true to the fundamental power.
Multiplier type power detectors give total, fundamental + harmonic power
measurements. It is of the author's opinion that the fundamental power is the more
appropriate parameter to control with the rf generator. Harmonic energy sourced from the
generator does not typically do much work in the plasma because the matching network
rejects much of this energy. It is the plasma-created harmonics that can do work in the
process. Nonlinear plasma-created harmonics, which are sourced from the fundamental ,
are more likely to be reflected off the matching network, back into the plasma/process.
Paul Rummel is an rf engineer at Comdel Inc. He has been
involved in rf design applications to the semiconductor industry for 18 years. He earned
his B.S. in electrical engineering at California Polytechnic State University and his M.S.
in electrical engineering at Michigan State University. Phone: 978-282-0620, ext. 133
e-mail: paul_rummel@comdel.com
Acknowledgments
The author would like to acknowledge Ken Smyth of Applied Materials, Steve Hilliker of
Novellus and John Caughman of Oak Ridge National Laboratory for their help with this
article. |