|
General Troubleshooting
for
Standard CX Series RF Generators
Note:
This guide would not be appropriate for units operating with DeviceNet
or for specialty products.
Current Situation:
Undoubtedly the world's most prolific user of
radio frequency (RF) generators is the semiconductor equipment industry.
Common practice within the semi industry is troubleshooting by swapping
parts - put in a new generator and if the problem goes away ship
the old one back for repair. This is a valid approach to troubleshooting
assuming that the parts are available to be swapped, but the mere
act of undoing all of the cables and reconnecting them to the new
equipment often "solves" the problem, which was a bad
cable or connection in the first place.
The Cost:
Also, in the clean room environment it is often
policy that once a component is removed from local stock it cannot
be returned. The result is that approximately 40% of all RF generators
returned to the manufacturer for repair are diagnosed "No Fault
Found." The cost of transporting, troubleshooting, and restocking
these perfectly good generators is enormous.
Comdel Approach:
This troubleshooting guide is intended to aid
the engineers and technicians on the firing line in determining
if an apparent RF problem is in the generator or outside the generator.
In the Rack Troubleshooting:
In order to confirm or eliminate the generator
as the problem in the RF system without uninstalling the generator
and without disturbing any of the wiring, the first pass should
be "in the rack" troubleshooting. A block diagram for
troubleshooting purposes can be as simple as Figure 1:
Put simply, the generator can be identified as
the cause of a problem only if the load and all of the inputs are
what they should be and the outputs aren't. So "in the rack"
troubleshooting to determine if a problem is inside or outside the
generator involves systematically checking the generator inputs
and the load environment. The troubleshooting guide below assumes
that the generator in question is one that has been on the system
and performing or is a part number that has been qualified on the
system and the system has been functional with a like part number.
Comdel part numbers always start with "FP"
followed by four digits, an "R" and then either a numeric
or alpha character referring to the revision level. This number
can be found on the serial number tag.
The first step should be to refer to the
product manual for the generator in question. Product manuals can
be found on Comdel's website. Use the part number as a reference
to ensure that you have the proper manual. Next, operate the generator
using the system controls in normal operating fashion. Refer to
Figure 2 for power measurement and other front panel indicators
and controls.
Tools and instruments required:
- Generator specification/manual defining
the I/O for the particular generator part number
- Digital Volt Meter (DVM)
- Cable Breakout so that voltage measurements
can be taken at the generator interface connector.
- An external power meter is not recommended
for "in the rack" troubleshooting. Forward and reflected
power information can be read on the generator display. This exercise
is primarily one of observation and low level voltage measurement.
If required, visual inspection of line voltage connections with
circuit breaker mains OFF is adequate to inspect for proper power
line input to the generator.

NOTE: In some cases the generator is programmed to control
on "delivered" power rather than forward power out. This
may be hard wired in the generator or selectable via a digital input
pin on the interface connector. In such a case, there will be a
DEL power indicator in place of the FWD power indicator and DEL
should be equal to setpoint plus RFL power.
| CX
Series Generator "In The Rack" Troubleshooting Guide |
| Problem |
Conditions and/or Symptom |
Probable External Cause(s) |
| Generator won't
power up |
No indicator lights
or display on front panel |
1. Generator circuit breaker off or tripped
2. Missing one or more legs of the power line
|
| |
Red
flashing light on right side of front panel (indicates that
the safety interlock loop is not satisfied) |
1. Missing RF output
connector interlock cover
2. No external connection between interface pins designated
as "safety interlock" |
| |
Steady red light
on right side of front panel |
Generator did not
autostart - possibly per specification. Push green button |
| Generator
powers up but no RF output |
Setpoint of
"0" indicated on generator front panel display |
No setpoint
input from system control |
| |
Generator
indicates proper setpoint but FWD and RFL power indicators not
shown on front panel display |
No "RF
enable" signal from system control |
| Some power out but less than
requested |
Reflected power is high but
not nearly as high as forward power (generator is in reflected
foldback) |
Impedance matching * |
| |
Reflected power is nearly as
high as forward power (generator is in reflected foldback and
almost no power is being delivered) |
1. A short or open circuit
in the coax, the match, or the match - load connection.
2. The matching network is not in a position to ignite the plasma.
3. The chamber pressure or other parameter is not proper for
plasma ignition. |
| |
Reflected power
is low (or zero) |
Missing one leg
of the three phase line |
| |
Setpoint on display
not in agreement with analog voltage from system control (25
pin analog interface only) |
1. Missing ground
reference on return side of differential analog input (external)
2. System noise |
| Requested
power out but excessive reflected |
|
Impedance
matching * |
| Generator overheats |
Operation is normal when generator
is cool, overheating happens after some seconds or minutes of
RF on. |
1. Excessively high ambient
air temperature
2. Insufficient air circulation in vicinity of generator
3. Insufficient cooling water flow
4. Excessive cooling water temperature |
| Power indicated on system controller disagrees
with generator power indication (fwd or ref). |
Analog interface in use (DeviceNet and RS-232
communication is not covered in this troubleshooting guide) |
1. Connection problem between generator
analog output and system control
2. Missing ground reference on return side of differential analog
output (external)
3. System noise
|
* In frequency tuning cases, high reflected power
can be caused by faulty tuning on the part of the generator. However,
this is highly unlikely in the case of a generator that has been
successfully qualified to operate into the load. All external causes
of high reflected power should be ruled out before suspecting the
generator.
On the Bench Troubleshooting:
If "in the rack"
troubleshooting is inconclusive or if it indicates a generator problem,
further investigation should be done with the generator operating
independently of the system. In this case the generator can be operated
in the "LOCAL" mode and the load should be a 50 ohm "dummy
load." If possible, a known good RF coaxial cable should be
used between the generator and the dummy load. If the generator
power measurement is suspect, an external power meter can be used
to measure power.
Refer to Figure 2 for previously discussed
indicators and controls and to Figure 3 for local operation of the
generator:

Setup:
- Connect line power,
water if needed, and dummy load with inline watt meter if desired.
- Provide safety interlock and RF enable
jumpers to the generator analog interface connector. Refer to
the generator specification if available (generally found at Comdel's
website).
- "Standard"
25 pin interface uses Pins 10 - 23 for safety interlock; Pins
6 - 4 and 17 - 19 for RF enable.
- "Standard"
15 pin interface uses Pins 11 - 12 for safety interlock and
Pins 4 - 9 for RF enable.
- Lack of safety
interlock will cause the red LED in the red "0"
button to flash on and off. Note that the plunger associated
with the RF output connector is part of the safety interlock
loop. Install the cover provided or pull out on the plunger.
- An attempt to
enable RF output with the interface RF enable pins not connected
will cause "Check RF Interlock" to be displayed
on the front panel of the generator.
Local Operation:
- Turn on the circuit breaker in the back
of the generator. In most cases the generator will "autostart"
when the breaker is turned on. In the rare cases when the specification
does not call for autostart, the generator is powered up by pushing
the green "1" button.
- The generator powers up in the REMote
mode. Toggle to LOCal mode using the "double arrow"
button.
- Dial in a setpoint using the "Manual
Input Wheel."
- Push the "Sine Wave" button
to enable RF output.
- The forward power output as indicated
on the generator display should equal the setpoint.
- Reflected power should be zero or
very close to zero. If this is not he case, the fault is probably
NOT in the generator. The coax cable between the generator
and dummy load is likely at fault.
Click
here for print friendly version
Comdel
Products | Sales
& Service | News
& Events | About
Comdel | Your
RF Resource | Site Map
| Contact Us | Home
|